Comandante Ferraz Antarctic Station

Comandante Ferraz Antarctic Station
Eron Costin©

Comandante Ferraz Antarctic Station

Design and build for Brazil in Antarctic

In certain places on the planet, nature creates adverse conditions for the human body. In these places, thinking about a building is almost like constructing a garment, an artifact that protects and provides comfort. This is a problem of technological performance, but one that must be combined with aesthetics. Making human beings feel comfortable involves more than addressing notions of comfort and safety; it also means working with spaces in their symbolic and perceptual dimensions.

photo_credit Eron Costin©
Eron Costin©
photo_credit Eron Costin©
Eron Costin©
photo_credit Eron Costin©
Eron Costin©
photo_credit Eron Costin©
Eron Costin©

A shelter, a safe place. Brazil’s new home in Antarctica. A place of protection and gathering for the production of scientific knowledge.

This is how the task of designing the new Comandante Ferraz Antarctic Station is approached.

The void left by the fire that occurred in 2012 carries symbolic significance for the importance of this new construction; it represents the Brazilian presence in Antarctica as an opportunity to contribute to scientific research together with the international community. It also represents an opportunity for technological development in Brazilian architecture and industry.

On the other hand, the design process gradually leads us to understand the fragility of human life and how one must act to solve construction, functional, and sensory problems. In this sense, decisions are made carefully, as it is necessary to respect nature and understand that there are challenges to be overcome before reaching the completed building.

photo_credit Eron Costin©
Eron Costin©
photo_credit Eron Costin©
Eron Costin©

The present proposal for Ferraz Station is based on an interpretation of the territory and the geographical conditions of the region. Therefore, the site layout of the proposed buildings takes into consideration the topography of Keller Peninsula and the need to preserve the surrounding areas of animal and plant life, among other factors. Several conditions established by the Environmental Land Use Zoning are respected in order to minimize impacts on nature.

The main building of the new station will have a total area of 4,500 m², while the isolated units, such as the wind turbine towers and the helicopter area, will add another 500 m².

The functional sectors are organized into blocks that distribute the different uses. The upper block houses the cabins, social areas, and central storage room. The lower block incorporates the laboratories, dining/living areas, and operation and maintenance areas. This same block houses the garages and technical areas.

photo_credit Leonardo Finotti ©
Leonardo Finotti ©
photo_credit Leonardo Finotti ©
Leonardo Finotti ©
photo_credit Leonardo Finotti ©
Leonardo Finotti ©

Logistics and Prefabrication Strategies

Comandante Ferraz Station was designed taking into consideration the need for the prefabrication and industrialization of building components. For this reason, the use of a continuous construction section throughout most of the building was chosen. The central strategy in this regard is the repetition of components and building systems, allowing for high levels of precision and quality during assembly and ensuring the building’s high performance, while also rationalizing the manufacturing process.

Structures and Building Materials

The materials selected were primarily those capable of meeting the various environmental performance requirements resulting from the construction of a building in Antarctica.

The main structures are designed in steel with high resistance to corrosion and cold climates, treated to minimize maintenance requirements. The steel structure supporting the floors consists of trusses arranged in a grid and is modularized into 600 × 1,200 cm panels, which can be prefabricated before being transported to the construction site.

photo_credit Leonardo Finotti ©
Leonardo Finotti ©
photo_credit Leonardo Finotti ©
Leonardo Finotti ©
photo_credit Leonardo Finotti ©
Leonardo Finotti ©
photo_credit Leonardo Finotti ©
Leonardo Finotti ©

The bracing of the structures supporting the roofs and walls is provided by transverse trussed walls positioned at intervals of no more than 12 meters.

Internally, various spaces can be prefabricated as components, such as the cabins and Isolated Units, for example. This makes it possible to transport these habitable units already assembled from Brazil, including their specific furniture.

Environmental Comfort Strategies

The main focus of the environmental comfort strategies was to improve the performance of the building envelope, preventing heat loss as much as possible.

Another relevant issue was defining the desired temperature profiles for each interior space of the station. Based on these definitions, the program was also grouped according to three factors: 1 — similar temperature profiles of the spaces; 2 — occupancy of the spaces throughout the day; 3 — seasonal occupancy of the station’s spaces, considering the difference between summer and the rest of the year.

Based on these initial parameters, a simulation was carried out to comparatively assess the possible performance of different insulation materials.

In order to achieve low thermal transmittance in the opaque elements of the building envelope, PUR (polyurethane) was selected. The thickness of this layer was defined as 21 cm based on specific simulations and comparative data.

photo_credit Leonardo Finotti ©
Leonardo Finotti ©
photo_credit Leonardo Finotti ©
Leonardo Finotti ©
photo_credit Leonardo Finotti ©
Leonardo Finotti ©

The EACF was simulated using software in order to understand the behavior of the heating system’s energy consumption. The objective was to determine the reduction in consumption resulting from variations in setpoints in spaces with different types of use, compared to a constant setpoint — the temperature that the HVAC system is required to reach — throughout all areas of the Station.

The simulation results showed that the most significant thermal load comes from outdoor air, both through infiltration and air renewal. Reducing outdoor air renewal rates provides a substantial decrease in the energy consumption required to heat the spaces.

However, air renewal is essential for maintaining indoor air quality. The impact of this load can be reduced through solutions such as preheating the outdoor air, using materials such as ceilings and finishes that reduce the amount of suspended particles, and using CO₂ concentration sensors, allowing the air renewal rate to be reduced according to the CO₂ concentration in the space.

Water, Wastewater, Solid Waste, and Energy Management

Based on the principle that potable water is a scarce resource, the systems were designed taking into account the need to reuse wastewater, treat greywater, and treat the generated sewage, in accordance with the parameters established in the competition brief.

The water and wastewater treatment plant is located below the upper block, where the demand for treated water is greatest, since the cabin restrooms are concentrated in this sector.

Regarding the energy required to maintain the station’s operation, a cogeneration model based on photovoltaic, wind, and diesel generator energy sources is proposed. System automation provides a balance between these sources, depending on the available power from each generation system.

photo_credit Leonardo Finotti ©
Leonardo Finotti ©

Another measure that can significantly reduce energy consumption is the scheduled shutdown of certain spaces, such as laboratories and some of the cabins, when they are unoccupied. During winter, these areas can be maintained at an indoor temperature of approximately 5°C solely to prevent pipes from freezing.

Systems and Installations

For heating, a radiant system is proposed, with radiators installed in each interior space. The radiators are individually connected to occupancy sensors and thermostats, which in turn send information to the automation system.

This system offers several advantages over radiant floor heating, for example. The radiator system is less expensive, easier to install, has lower operating costs, and allows for optimized zoning by space. In other words, if a radiator is not operating, it can be switched off independently from the rest of the system.

photo_credit Leonardo Finotti ©
Leonardo Finotti ©

Fire Protection and Firefighting Strategies

The strategy proposed for fire safety at Comandante Ferraz Station is based on the following principles: a — risk compartmentalization/isolation; b — provision of fire barriers; c — adoption of complementary firefighting systems.

The building is organized into autonomous units with individualized fire protection systems. The main system used is an automatic sprinkler system, but in specific cases — engines, boilers, generators, and control rooms — water mist systems are used, complemented by clean agents. To isolate the station’s sectors, double walls are provided, which also contain the main emergency exits and areas with fire-rated doors and fire-protected vestibules.